Search:
Web
Site
Go
Company
Production Program
Products
Multitronik 592
LON-Center 2000
GW 399
MWS 906
MWS 906 CP
MWS 903
MWS 897
ITR 498
ITR 504
Biogas 401
Biogas 905
KM 2000 CnHm EM
KM 2000 Accessories
RG 399
GWA 2000
GTR 210
GTR 196
TOX 592
LCTR 903
Log & View Software
Filter-Guard 206
Accessories
Jobs and Career
Contact
Download PDF
ADOS GmbH
Instrumentation and Control
Trierer Strasse 23 – 25
52078 Aachen
FRG
Phone: +49 (0)241 / 9769 - 0
Fax: +49 (0)241 / 9769 - 16
info@ados.de
Login
Filter-Guard 206
| Dust Filter Monitoring
Application
Filter-Guard 206
continuously monitors the clean air side of any fine dust filter installations.
A warning is initiated when a sudden increase in dust concentration is present, i.e. due to breakdown in the filter casing or bag.
Fields of Application
Monitoring filter systems
Vibrating and jet filter systems
Air extraction installations in wood and plastic processing plants
Air conditioning units with dust filter systems
Paint and varnish production
Ambient air monitoring at workplaces
and many more
Features
Suitable for various types of dust
4-20mA standard output signal
LON
®
interface (optional)
Low current consumption
Robust aluminium housing
Straightforward installation
Easy exchange of the sensor elements
Detectable Types of Dust
Dust types:
Wood dust
Household dust
Colouring pigments
Plastic dust
Flour dust
Metallic dust
Mineral dust
and many more
Evaluation Units
Multi-channel installations:
MWS 897
MWS 903
LON
®
-Center 2000
GW 399
Multitronik MC 602
Accessories
Signal horns, warning lamps, warning banners, air control accessories, metering units, plotters, data-logger.
Further accessories can be supplied on request, according to the proposed measurement tasks.
Technical Data
Measurement
principle:
optical light dispersion
Fields of application:
filtermonitoring for dry, not sticking, not lumping, not hygroscopic substances
Measurement ranges:
0 – 100 % dust
approx. measurement range:
total dust
0.1 - 20 mg / m
3
0.1 - 50 mg / m
3
0.1 - 100 mg / m
3
dependant on the kind of dust at the measuring point
Medium humidity:
dry
Measurement accuracy:
pure warning function, no metering unit
Ambient temperature:
14 °F to 122 °F
Response time (t
90
):
< 10 s
Installation:
flexible flange for output air channel construction (flat and round channels)
Protection class:
IP 54
Output signals:
analog output 4 (0)-20 mA
RS 485 / LON
®
Voltage supply:
24 V DC
Power consumption:
3 VA
Dimensions
(D x L):
1.97 x 11.8 inch or
1.97 x 23.6 inch (long version)
Weight:
approx. 2.09 lbs
Trademark right:
EU-patent
Product data sheet
Filter-Guard 206
home
top
sitemap
conditions of use
imprint